ED-A-A-325AC6-B24 C
2.29 kW
Defrost: None
Product code: ED-A-A-325BC6-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,524 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 7.7 m² |
| Inner volume | 2.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 16 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 59.7 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-A-A-325BC6-B24 C | None |
|---|---|
| ED-A-A-325BC6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.97 | 0.96 | 0.96 | 0.96 | 0.95 | 0.95 | 0.94 | 0.96 | 1.03 | 1.11 | 1.09 | 1.09 | 1.08 | 1.06 |
| 5 | 1.28 | 1.27 | 1.28 | 1.29 | 1.29 | 1.28 | 1.27 | 1.29 | 1.37 | 1.49 | 1.44 | 1.43 | 1.41 | 1.38 |
| 6 | 1.58 | 1.59 | 1.61 | 1.63 | 1.64 | 1.64 | 1.62 | 1.64 | 1.74 | 1.88 | 1.82 | 1.80 | 1.77 | 1.71 |
| 7 | 1.88 | 1.91 | 1.95 | 1.98 | 2.00 | 2.00 | 1.99 | 2.01 | 2.13 | 2.30 | 2.22 | 2.19 | 2.15 | 2.08 |
| 8 | 2.16 | 2.22 | 2.27 | 2.33 | 2.36 | 2.37 | 2.36 | 2.38 | 2.52 | 2.73 | 2.65 | 2.61 | 2.56 | 2.47 |
| 9 | 2.43 | 2.51 | 2.59 | 2.67 | 2.72 | 2.74 | 2.74 | 2.77 | 2.93 | 3.17 | 3.08 | 3.04 | 2.97 | 2.87 |
| 10 | 2.68 | 2.78 | 2.89 | 2.98 | 3.05 | 3.09 | 3.10 | 3.14 | 3.33 | 3.61 | 3.51 | 3.47 | 3.40 | 3.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.513 |
| SC2 | 0 | 8 | 2.382 |
| SC3 | -18 | 7 | 1.990 |
| SC4 | -25 | 6 | 1.612 |
| SC5 | -34 | 6 | 1.585 |
| A | 570 mm |
|---|---|
| B | 1200 mm |
| C | 150 mm |
| E | 970 mm |
| D | 300 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 570 mm |
|---|---|
| Width | 1200 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.