ED-A-A-325BC6-B24 C
2.49 kW
Defrost: None
Product code: ED-A-A-325AC6-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,525 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 7.5 m² |
| Inner volume | 2.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 15 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 59.7 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-A-A-325AC6-B24 C | None |
|---|---|
| ED-A-A-325AC6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.88 | 0.86 | 0.85 | 0.84 | 0.83 | 0.82 | 0.81 | 0.83 | 0.89 | 0.96 | 0.94 | 0.93 | 0.92 | 0.90 |
| 5 | 1.18 | 1.17 | 1.16 | 1.16 | 1.15 | 1.13 | 1.11 | 1.13 | 1.20 | 1.30 | 1.26 | 1.25 | 1.23 | 1.21 |
| 6 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.47 | 1.45 | 1.46 | 1.55 | 1.67 | 1.61 | 1.59 | 1.56 | 1.52 |
| 7 | 1.80 | 1.81 | 1.82 | 1.84 | 1.84 | 1.83 | 1.81 | 1.81 | 1.92 | 2.07 | 1.99 | 1.96 | 1.92 | 1.85 |
| 8 | 2.10 | 2.12 | 2.16 | 2.19 | 2.20 | 2.20 | 2.17 | 2.18 | 2.31 | 2.49 | 2.40 | 2.36 | 2.31 | 2.22 |
| 9 | 2.38 | 2.43 | 2.49 | 2.54 | 2.56 | 2.56 | 2.55 | 2.56 | 2.71 | 2.92 | 2.82 | 2.78 | 2.72 | 2.61 |
| 10 | 2.64 | 2.71 | 2.79 | 2.86 | 2.90 | 2.93 | 2.92 | 2.94 | 3.11 | 3.36 | 3.25 | 3.21 | 3.13 | 3.01 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.253 |
| SC2 | 0 | 8 | 2.181 |
| SC3 | -18 | 7 | 1.841 |
| SC4 | -25 | 6 | 1.488 |
| SC5 | -34 | 6 | 1.494 |
| A | 570 mm |
|---|---|
| B | 1200 mm |
| C | 150 mm |
| E | 970 mm |
| D | 300 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 570 mm |
|---|---|
| Width | 1200 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.