ED-DP-235AC4-B22 C
7.20 kW
Defrost: None
Product code: ED-DP-145AC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,579 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 32.5 m² |
| Inner volume | 7.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 72 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-145AC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.78 | 2.78 | 2.79 | 2.81 | 2.82 | 2.81 | 2.79 | 2.85 | 3.04 | 3.30 | 3.24 | 3.22 | 3.19 | 3.14 |
| 5 | 3.63 | 3.67 | 3.72 | 3.77 | 3.79 | 3.78 | 3.76 | 3.82 | 4.05 | 4.40 | 4.29 | 4.26 | 4.21 | 4.14 |
| 6 | 4.48 | 4.59 | 4.69 | 4.78 | 4.82 | 4.83 | 4.81 | 4.86 | 5.15 | 5.58 | 5.42 | 5.37 | 5.29 | 5.16 |
| 7 | 5.26 | 5.46 | 5.65 | 5.80 | 5.89 | 5.93 | 5.91 | 5.96 | 6.32 | 6.84 | 6.64 | 6.56 | 6.45 | 6.26 |
| 8 | 5.94 | 6.22 | 6.47 | 6.70 | 6.83 | 6.92 | 6.96 | 7.04 | 7.48 | 8.12 | 7.91 | 7.81 | 7.67 | 7.43 |
| 9 | 6.56 | 6.93 | 7.24 | 7.54 | 7.75 | 7.87 | 7.93 | 8.03 | 8.53 | 9.26 | 9.04 | 8.95 | 8.80 | 8.56 |
| 10 | 7.13 | 7.57 | 8.00 | 8.38 | 8.65 | 8.82 | 8.91 | 9.03 | 9.59 | 10.40 | 10.17 | 10.06 | 9.90 | 9.61 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.169 |
| SC2 | 0 | 8 | 7.044 |
| SC3 | -18 | 7 | 5.848 |
| SC4 | -25 | 6 | 4.694 |
| SC5 | -34 | 6 | 4.505 |
| A | 1148 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1148 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.