ED-DP-145AC4-B24 C
7.32 kW
Defrost: None
Product code: ED-DP-145AE7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,445 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 30.5 m² |
| Inner volume | 10.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 74 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-145AE7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.97 | 2.93 | 2.91 | 2.91 | 2.91 | 2.89 | 2.87 | 2.93 | 3.12 | 3.39 | 3.33 | 3.31 | 3.28 | 3.23 |
| 5 | 3.90 | 3.88 | 3.88 | 3.90 | 3.89 | 3.87 | 3.83 | 3.89 | 4.13 | 4.48 | 4.36 | 4.32 | 4.27 | 4.20 |
| 6 | 4.83 | 4.85 | 4.89 | 4.93 | 4.94 | 4.92 | 4.88 | 4.92 | 5.21 | 5.64 | 5.47 | 5.41 | 5.33 | 5.19 |
| 7 | 5.74 | 5.81 | 5.90 | 5.98 | 6.02 | 6.01 | 5.97 | 6.00 | 6.36 | 6.87 | 6.65 | 6.57 | 6.44 | 6.24 |
| 8 | 6.64 | 6.78 | 6.92 | 7.04 | 7.11 | 7.13 | 7.09 | 7.12 | 7.54 | 8.15 | 7.89 | 7.78 | 7.62 | 7.36 |
| 9 | 7.47 | 7.70 | 7.91 | 8.11 | 8.22 | 8.25 | 8.23 | 8.27 | 8.76 | 9.46 | 9.17 | 9.04 | 8.85 | 8.53 |
| 10 | 8.24 | 8.56 | 8.85 | 9.13 | 9.30 | 9.38 | 9.38 | 9.43 | 9.99 | 10.79 | 10.47 | 10.33 | 10.11 | 9.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.472 |
| SC2 | 0 | 8 | 7.124 |
| SC3 | -18 | 7 | 6.004 |
| SC4 | -25 | 6 | 4.886 |
| SC5 | -34 | 6 | 4.839 |
| A | 1148 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 835 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1148 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.