ED-DP-235AE4-B22 C
8.20 kW
Defrost: None
Product code: ED-DP-240AC7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,996 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 30.5 m² |
| Inner volume | 10.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 93 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.3 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-240AC7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.96 | 3.01 | 3.06 | 3.11 | 3.13 | 3.13 | 3.11 | 3.17 | 3.37 | 3.66 | 3.58 | 3.55 | 3.51 | 3.44 |
| 5 | 3.81 | 3.94 | 4.06 | 4.17 | 4.23 | 4.25 | 4.25 | 4.31 | 4.58 | 4.96 | 4.84 | 4.80 | 4.74 | 4.66 |
| 6 | 4.64 | 4.86 | 5.07 | 5.25 | 5.35 | 5.42 | 5.44 | 5.51 | 5.85 | 6.35 | 6.20 | 6.14 | 6.05 | 5.91 |
| 7 | 5.37 | 5.69 | 5.98 | 6.25 | 6.44 | 6.57 | 6.63 | 6.74 | 7.16 | 7.78 | 7.60 | 7.53 | 7.42 | 7.23 |
| 8 | 5.99 | 6.42 | 6.81 | 7.12 | 7.38 | 7.57 | 7.68 | 7.82 | 8.32 | 9.07 | 8.90 | 8.83 | 8.71 | 8.51 |
| 9 | 6.56 | 7.10 | 7.54 | 7.99 | 8.33 | 8.57 | 8.73 | 8.90 | 9.48 | 10.33 | 10.15 | 10.07 | 9.93 | 9.69 |
| 10 | ≈ 7.07 | 7.67 | 8.28 | 8.83 | 9.25 | 9.56 | 9.77 | 9.98 | 10.64 | 11.60 | 11.41 | 11.31 | 11.16 | 10.89 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.410 |
| SC2 | 0 | 8 | 7.819 |
| SC3 | -18 | 7 | 6.336 |
| SC4 | -25 | 6 | 5.065 |
| SC5 | -34 | 6 | 4.688 |
| A | 1548 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.