ED-DP-335AC7-B22 C
8.76 kW
Defrost: None
Product code: ED-DP-145AE4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,174 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 48.7 m² |
| Inner volume | 10.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 79 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-145AE4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.64 | 3.64 | 3.66 | 3.69 | 3.70 | 3.70 | 3.68 | 3.78 | 4.03 | 4.38 | 4.30 | 4.28 | 4.25 | 4.20 |
| 5 | 4.66 | 4.69 | 4.75 | 4.81 | 4.83 | 4.83 | 4.79 | 4.87 | 5.18 | 5.63 | 5.48 | 5.43 | 5.36 | 5.25 |
| 6 | 5.65 | 5.75 | 5.85 | 5.95 | 6.00 | 6.00 | 5.96 | 6.03 | 6.40 | 6.93 | 6.73 | 6.65 | 6.53 | 6.34 |
| 7 | 6.63 | 6.80 | 6.96 | 7.10 | 7.19 | 7.21 | 7.17 | 7.23 | 7.65 | 8.28 | 8.03 | 7.92 | 7.76 | 7.49 |
| 8 | 7.53 | 7.79 | 8.04 | 8.26 | 8.39 | 8.42 | 8.39 | 8.45 | 8.95 | 9.67 | 9.37 | 9.24 | 9.04 | 8.70 |
| 9 | 8.36 | 8.72 | 9.05 | 9.35 | 9.54 | 9.64 | 9.63 | 9.69 | 10.26 | 11.06 | 10.73 | 10.58 | 10.34 | 9.93 |
| 10 | 9.11 | 9.58 | 10.01 | 10.39 | 10.60 | 10.73 | 10.77 | 10.87 | 11.52 | 12.46 | 12.11 | 11.94 | 11.66 | 11.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.112 |
| SC2 | 0 | 8 | 8.449 |
| SC3 | -18 | 7 | 7.142 |
| SC4 | -25 | 6 | 5.850 |
| SC5 | -34 | 6 | 5.675 |
| A | 1148 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 835 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1148 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.