ED-DP-145AC7-B24 C
5.81 kW
Defrost: None
Product code: ED-DP-235AC7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,362 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 22.9 m² |
| Inner volume | 8.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 82 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 63.0 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-235AC7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.23 | 2.20 | 2.20 | 2.20 | 2.20 | 2.19 | 2.17 | 2.22 | 2.36 | 2.56 | 2.51 | 2.49 | 2.46 | 2.42 |
| 5 | 2.93 | 2.94 | 2.95 | 2.97 | 2.98 | 2.96 | 2.94 | 2.98 | 3.16 | 3.43 | 3.34 | 3.32 | 3.28 | 3.22 |
| 6 | 3.63 | 3.68 | 3.73 | 3.78 | 3.80 | 3.80 | 3.77 | 3.81 | 4.04 | 4.37 | 4.25 | 4.20 | 4.14 | 4.04 |
| 7 | 4.33 | 4.43 | 4.51 | 4.60 | 4.65 | 4.66 | 4.65 | 4.68 | 4.96 | 5.37 | 5.21 | 5.15 | 5.06 | 4.92 |
| 8 | 4.98 | 5.14 | 5.29 | 5.43 | 5.51 | 5.54 | 5.54 | 5.58 | 5.92 | 6.41 | 6.23 | 6.15 | 6.04 | 5.87 |
| 9 | 5.57 | 5.79 | 6.01 | 6.21 | 6.34 | 6.43 | 6.45 | 6.50 | 6.89 | 7.46 | 7.26 | 7.18 | 7.05 | 6.84 |
| 10 | 6.10 | 6.40 | 6.68 | 6.93 | 7.08 | 7.19 | 7.26 | 7.35 | 7.81 | 8.48 | 8.29 | 8.21 | 8.08 | 7.84 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.294 |
| SC2 | 0 | 8 | 5.582 |
| SC3 | -18 | 7 | 4.622 |
| SC4 | -25 | 6 | 3.727 |
| SC5 | -34 | 6 | 3.648 |
| A | 1548 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.