ED-DP-245AE4-B24 C
17.36 kW
Defrost: None
Product code: ED-DP-345AC7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,426 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 60.6 m² |
| Inner volume | 19.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 152 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 570 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.2 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-345AC7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.29 | 6.21 | 6.18 | 6.17 | 6.13 | 6.08 | 6.02 | 6.09 | 6.45 | 6.97 | 6.80 | 6.74 | 6.65 | 6.52 |
| 5 | 8.39 | 8.40 | 8.44 | 8.49 | 8.48 | 8.43 | 8.34 | 8.40 | 8.91 | 9.63 | 9.37 | 9.28 | 9.15 | 8.97 |
| 6 | 10.50 | 10.62 | 10.78 | 10.94 | 10.99 | 10.98 | 10.90 | 10.96 | 11.61 | 12.54 | 12.17 | 12.04 | 11.84 | 11.56 |
| 7 | 12.49 | 12.83 | 13.15 | 13.44 | 13.60 | 13.63 | 13.59 | 13.67 | 14.48 | 15.66 | 15.20 | 15.02 | 14.76 | 14.35 |
| 8 | 14.26 | 14.79 | 15.30 | 15.76 | 16.08 | 16.28 | 16.37 | 16.45 | 17.43 | 18.89 | 18.37 | 18.16 | 17.85 | 17.34 |
| 9 | 15.85 | 16.59 | 17.28 | 17.83 | 18.27 | 18.56 | 18.72 | 18.94 | 20.12 | 21.86 | 21.40 | 21.20 | 20.90 | 20.40 |
| 10 | 17.33 | 18.30 | 19.10 | 19.91 | 20.47 | 20.86 | 21.09 | 21.36 | 22.70 | 24.67 | 24.17 | 23.95 | 23.61 | 23.03 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.172 |
| SC2 | 0 | 8 | 16.453 |
| SC3 | -18 | 7 | 13.520 |
| SC4 | -25 | 6 | 10.782 |
| SC5 | -34 | 6 | 10.551 |
| A | 2748 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 2435 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.