ED-DP-445AC7-B24 C
23.27 kW
Defrost: None
Product code: ED-DP-345AE4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,521 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 146.1 m² |
| Inner volume | 31.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 190 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 570 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | B |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø42 |
| ED-DP-345AE4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.31 | 10.63 | 10.93 | 11.21 | 11.36 | 11.42 | 11.38 | 11.69 | 12.47 | 13.57 | 13.30 | 13.22 | 13.10 | 12.95 |
| 5 | 12.95 | 13.51 | 14.04 | 14.45 | 14.74 | 14.87 | 14.86 | 15.14 | 16.10 | 17.50 | 17.04 | 16.87 | 16.61 | 16.19 |
| 6 | 15.29 | 16.18 | 16.99 | 17.69 | 18.15 | 18.39 | 18.41 | 18.69 | 19.81 | 21.53 | 20.94 | 20.70 | 20.32 | 19.70 |
| 7 | 17.37 | 18.55 | 19.64 | 20.46 | 21.14 | 21.55 | 21.71 | 22.07 | 23.45 | 25.48 | 24.85 | 24.57 | 24.14 | 23.33 |
| 8 | 19.23 | 20.75 | 22.00 | 23.24 | 24.13 | 24.68 | 24.95 | 25.36 | 26.94 | 29.25 | 28.56 | 28.22 | 27.70 | 26.78 |
| 9 | ≈ 20.90 | 22.61 | 24.34 | 25.89 | 27.03 | 27.77 | 28.16 | 28.65 | 30.44 | 33.04 | 32.28 | 31.90 | 31.30 | 30.22 |
| 10 | 22.40 | 24.45 | 26.54 | 28.43 | 29.84 | 30.81 | 31.35 | 31.92 | 33.93 | 36.84 | 36.03 | 35.60 | 34.93 | 33.70 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.029 |
| SC2 | 0 | 8 | 25.357 |
| SC3 | -18 | 7 | 20.773 |
| SC4 | -25 | 6 | 16.985 |
| SC5 | -34 | 6 | 15.498 |
| A | 2748 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 2435 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø42 |
| Length | 2748 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |