ED-DP-440AC7-B22 C
16.68 kW
Defrost: None
Product code: ED-DP-435AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,612 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 108.8 m² |
| Inner volume | 21.0 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 160 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | A |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| ED-DP-435AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.55 | 6.74 | 6.91 | 7.07 | 7.17 | 7.20 | 7.18 | 7.35 | 7.84 | 8.53 | 8.35 | 8.29 | 8.20 | 8.08 |
| 5 | 8.15 | 8.48 | 8.80 | 9.07 | 9.24 | 9.31 | 9.31 | 9.46 | 10.06 | 10.93 | 10.64 | 10.53 | 10.36 | 10.08 |
| 6 | 9.70 | 10.20 | 10.67 | 11.07 | 11.33 | 11.45 | 11.47 | 11.63 | 12.34 | 13.40 | 13.03 | 12.87 | 12.63 | 12.22 |
| 7 | 11.04 | 11.73 | 12.37 | 12.93 | 13.31 | 13.48 | 13.57 | 13.77 | 14.62 | 15.86 | 15.43 | 15.24 | 14.93 | 14.41 |
| 8 | 12.24 | 13.14 | 13.97 | 14.60 | 15.12 | 15.43 | 15.58 | 15.80 | 16.78 | 18.20 | 17.76 | 17.54 | 17.20 | 16.61 |
| 9 | ≈ 13.32 | 14.44 | 15.36 | 16.28 | 16.94 | 17.36 | 17.57 | 17.83 | 18.94 | 20.54 | 20.05 | 19.80 | 19.42 | 18.73 |
| 10 | ≈ 14.29 | 15.52 | 16.77 | 17.88 | 18.71 | 19.25 | 19.55 | 19.86 | 21.10 | 22.88 | 22.35 | 22.08 | 21.65 | 20.87 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.354 |
| SC2 | 0 | 8 | 15.800 |
| SC3 | -18 | 7 | 13.103 |
| SC4 | -25 | 6 | 10.667 |
| SC5 | -34 | 6 | 9.813 |
| A | 2748 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.