ED-DR-363AA5-A29 C
40.16 kW
Defrost: None
Product code: ED-DR-563AA5-A29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 89,722 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 323.0 m² |
| Inner volume | 67.7 dm³ |
| Fin spacing | 5.0 mm |
| Fin material | Aluminium |
| Net weight | 534 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-DR-563AA5-A29 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 24.57 | ≈ 25.18 | ≈ 25.69 | ≈ 25.94 | ≈ 26.02 | ≈ 25.96 | ≈ 25.98 | ≈ 27.50 | ≈ 29.73 | ≈ 28.97 | ≈ 28.70 | ≈ 28.32 | ≈ 27.74 |
| 5 | ≈ 30.32 | ≈ 31.68 | ≈ 33.08 | ≈ 34.27 | ≈ 35.01 | ≈ 35.43 | ≈ 35.62 | ≈ 35.77 | ≈ 37.92 | ≈ 41.04 | ≈ 40.07 | ≈ 39.70 | ≈ 39.15 | ≈ 38.29 |
| 6 | ≈ 35.48 | ≈ 37.78 | 39.87 | ≈ 41.72 | ≈ 43.05 | ≈ 43.98 | ≈ 44.62 | ≈ 45.15 | ≈ 48.01 | ≈ 52.21 | ≈ 51.33 | ≈ 50.97 | ≈ 50.44 | ≈ 49.57 |
| 7 | ≈ 40.16 | ≈ 43.32 | ≈ 46.24 | ≈ 48.83 | ≈ 50.74 | ≈ 52.11 | ≈ 53.07 | ≈ 53.83 | ≈ 57.29 | ≈ 62.35 | ≈ 61.37 | ≈ 60.96 | ≈ 60.34 | ≈ 59.29 |
| 8 | ≈ 44.35 | ≈ 48.43 | ≈ 52.24 | ≈ 55.67 | ≈ 58.27 | ≈ 60.18 | ≈ 61.54 | 62.58 | ≈ 66.66 | ≈ 72.64 | ≈ 71.60 | ≈ 71.15 | ≈ 70.46 | ≈ 69.26 |
| 9 | ≈ 48.10 | ≈ 53.10 | ≈ 57.88 | ≈ 62.21 | ≈ 65.58 | ≈ 68.10 | ≈ 69.95 | ≈ 71.34 | ≈ 76.07 | ≈ 83.01 | ≈ 81.96 | ≈ 81.48 | ≈ 80.73 | ≈ 79.42 |
| 10 | ≈ 29.75 | ≈ 57.34 | ≈ 63.11 | ≈ 68.41 | ≈ 72.62 | ≈ 75.86 | ≈ 78.26 | ≈ 80.07 | ≈ 85.46 | ≈ 93.38 | 92.38 | ≈ 91.89 | ≈ 91.12 | ≈ 89.71 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | ≈ 25.46 | ≈ 25.98 | ≈ 26.24 | ≈ 26.32 | ≈ 26.27 | ≈ 26.28 | ≈ 27.82 | ≈ 30.03 | ≈ 29.30 | ≈ 29.03 | ≈ 28.64 | ≈ 28.04 |
| 5 | ≈ 30.58 | ≈ 31.98 | ≈ 33.43 | ≈ 34.66 | ≈ 35.44 | ≈ 35.87 | ≈ 36.07 | ≈ 36.23 | ≈ 38.41 | ≈ 41.57 | ≈ 40.59 | ≈ 40.21 | ≈ 39.65 | ≈ 38.77 |
| 6 | ≈ 35.73 | ≈ 38.08 | 40.22 | ≈ 42.12 | ≈ 43.48 | ≈ 44.43 | ≈ 45.09 | ≈ 45.63 | ≈ 48.53 | ≈ 52.77 | ≈ 51.89 | ≈ 51.53 | ≈ 50.99 | ≈ 50.11 |
| 7 | ≈ 40.42 | ≈ 43.65 | ≈ 46.63 | ≈ 49.29 | ≈ 51.25 | ≈ 52.66 | ≈ 53.64 | ≈ 54.41 | ≈ 57.92 | ≈ 63.04 | ≈ 62.05 | ≈ 61.64 | ≈ 61.01 | ≈ 59.95 |
| 8 | ≈ 44.61 | ≈ 48.78 | ≈ 52.68 | ≈ 56.18 | ≈ 58.84 | ≈ 60.80 | ≈ 62.20 | 63.26 | ≈ 67.40 | ≈ 73.45 | ≈ 72.41 | ≈ 71.95 | ≈ 71.25 | ≈ 70.05 |
| 9 | ≈ 48.43 | ≈ 53.47 | ≈ 58.33 | ≈ 62.76 | ≈ 66.21 | ≈ 68.80 | ≈ 70.70 | ≈ 72.12 | ≈ 76.91 | ≈ 83.94 | ≈ 82.89 | ≈ 82.41 | ≈ 81.66 | ≈ 80.33 |
| 10 | ≈ 28.58 | ≈ 57.71 | ≈ 63.59 | ≈ 69.00 | ≈ 73.31 | ≈ 76.62 | ≈ 79.09 | ≈ 80.95 | ≈ 86.41 | ≈ 94.43 | 93.43 | ≈ 92.95 | ≈ 92.17 | ≈ 90.75 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 92.376 | 93.429 |
| SC2 | 0 | 8 | 62.575 | 63.261 |
| SC3 | -18 | 7 | 49.664 | 50.144 |
| SC4 | -25 | 6 | 39.866 | 40.222 |
| SC5 | -34 | 6 | 36.016 | 36.274 |
| A | 5968 mm |
|---|---|
| B | 1730 mm |
| C | 788 mm |
| F | 1530 mm |
| G | 805 mm |
| E1 | 1138 mm |
| E2 | 1120 mm |
| E | 5635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 5968 mm |
|---|---|
| Width | 1730 mm |
| Height | 805 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.