EA-135AG4-C01 C
4.89 kW
Defrost: None
Product code: EA-230BE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,669 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 17.5 m² |
| Inner volume | 8.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.1 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-230BE10-C01 C | None |
|---|---|
| EA-230BE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.97 | 1.93 | 1.90 | 1.90 | 1.89 | 1.87 | 1.85 | 1.89 | 2.01 | 2.18 | 2.13 | 2.11 | 2.09 | 2.05 |
| 5 | 2.63 | 2.58 | 2.57 | 2.56 | 2.55 | 2.53 | 2.50 | 2.53 | 2.68 | 2.90 | 2.83 | 2.81 | 2.77 | 2.72 |
| 6 | 3.29 | 3.26 | 3.26 | 3.27 | 3.26 | 3.24 | 3.21 | 3.22 | 3.42 | 3.69 | 3.58 | 3.55 | 3.49 | 3.41 |
| 7 | 3.96 | 3.95 | 3.97 | 4.00 | 4.00 | 3.98 | 3.95 | 3.96 | 4.19 | 4.53 | 4.39 | 4.34 | 4.26 | 4.13 |
| 8 | 4.61 | 4.63 | 4.68 | 4.73 | 4.75 | 4.75 | 4.72 | 4.73 | 5.00 | 5.40 | 5.24 | 5.17 | 5.07 | 4.91 |
| 9 | 5.26 | 5.30 | 5.39 | 5.47 | 5.51 | 5.52 | 5.50 | 5.52 | 5.84 | 6.30 | 6.11 | 6.03 | 5.91 | 5.71 |
| 10 | 5.86 | 5.98 | 6.10 | 6.22 | 6.28 | 6.30 | 6.29 | 6.32 | 6.69 | 7.22 | 7.01 | 6.92 | 6.78 | 6.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.012 |
| SC2 | 0 | 8 | 4.728 |
| SC3 | -18 | 7 | 3.999 |
| SC4 | -25 | 6 | 3.259 |
| SC5 | -34 | 6 | 3.291 |
| A | 1357 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.