EA-340AC4-C01 C
15.41 kW
Defrost: None
Product code: EA-245AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,749 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 44.5 m² |
| Inner volume | 17.0 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 92 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-245AE8-C01 C | None |
|---|---|
| EA-245AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.59 | 5.52 | 5.48 | 5.46 | 5.41 | 5.34 | 5.26 | 5.36 | 5.66 | 6.11 | 5.94 | 5.88 | 5.80 | 5.68 |
| 5 | 7.50 | 7.52 | 7.55 | 7.58 | 7.55 | 7.47 | 7.36 | 7.46 | 7.91 | 8.54 | 8.30 | 8.22 | 8.11 | 7.95 |
| 6 | 9.41 | 9.52 | 9.67 | 9.81 | 9.84 | 9.79 | 9.67 | 9.77 | 10.35 | 11.17 | 10.81 | 10.68 | 10.50 | 10.24 |
| 7 | 11.18 | 11.52 | 11.82 | 12.08 | 12.21 | 12.20 | 12.11 | 12.21 | 12.93 | 13.96 | 13.49 | 13.31 | 13.05 | 12.64 |
| 8 | 12.78 | 13.28 | 13.76 | 14.19 | 14.46 | 14.61 | 14.62 | 14.71 | 15.58 | 16.86 | 16.32 | 16.11 | 15.79 | 15.26 |
| 9 | 14.19 | 14.89 | 15.54 | 16.05 | 16.43 | 16.66 | 16.75 | 16.96 | 18.00 | 19.54 | 19.06 | 18.85 | 18.54 | 17.97 |
| 10 | 15.51 | 16.42 | 17.17 | 17.91 | 18.41 | 18.73 | 18.88 | 19.13 | 20.32 | 22.05 | 21.53 | 21.29 | 20.94 | 20.33 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.530 |
| SC2 | 0 | 8 | 14.713 |
| SC3 | -18 | 7 | 12.149 |
| SC4 | -25 | 6 | 9.673 |
| SC5 | -34 | 6 | 9.451 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.