EA-230BE4-C01 C
6.20 kW
Defrost: None
Product code: EA-330AC6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,469 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 23.7 m² |
| Inner volume | 7.1 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AC6-C05 C | None |
|---|---|
| EA-330AC6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.37 | 2.35 | 2.34 | 2.35 | 2.34 | 2.33 | 2.31 | 2.37 | 2.52 | 2.73 | 2.68 | 2.66 | 2.63 | 2.59 |
| 5 | 3.14 | 3.14 | 3.15 | 3.17 | 3.17 | 3.16 | 3.13 | 3.18 | 3.38 | 3.66 | 3.57 | 3.54 | 3.50 | 3.45 |
| 6 | 3.89 | 3.94 | 3.99 | 4.04 | 4.06 | 4.05 | 4.02 | 4.06 | 4.31 | 4.66 | 4.53 | 4.48 | 4.41 | 4.31 |
| 7 | 4.64 | 4.74 | 4.84 | 4.92 | 4.97 | 4.98 | 4.95 | 4.99 | 5.29 | 5.73 | 5.55 | 5.49 | 5.39 | 5.23 |
| 8 | 5.34 | 5.51 | 5.67 | 5.82 | 5.91 | 5.94 | 5.92 | 5.96 | 6.32 | 6.84 | 6.64 | 6.55 | 6.43 | 6.22 |
| 9 | 5.94 | 6.18 | 6.41 | 6.61 | 6.75 | 6.81 | 6.85 | 6.93 | 7.35 | 7.97 | 7.74 | 7.64 | 7.49 | 7.23 |
| 10 | 6.51 | 6.83 | 7.12 | 7.36 | 7.53 | 7.65 | 7.70 | 7.80 | 8.28 | 8.98 | 8.77 | 8.68 | 8.52 | 8.26 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.771 |
| SC2 | 0 | 8 | 5.962 |
| SC3 | -18 | 7 | 4.949 |
| SC4 | -25 | 6 | 3.987 |
| SC5 | -34 | 6 | 3.904 |
| A | 1657 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 450.5 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.