EA-250AC6-C10 C
18.16 kW
Defrost: None
Product code: EA-535AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,022 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 54.8 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 104 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-535AC6-C01 C | None |
|---|---|
| EA-535AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.69 | 6.74 | 6.80 | 6.85 | 6.85 | 6.81 | 6.74 | 6.87 | 7.28 | 7.87 | 7.67 | 7.59 | 7.49 | 7.33 |
| 5 | 8.81 | 9.03 | 9.20 | 9.38 | 9.45 | 9.45 | 9.38 | 9.53 | 10.12 | 10.95 | 10.67 | 10.57 | 10.44 | 10.24 |
| 6 | 10.76 | 11.18 | 11.58 | 11.94 | 12.18 | 12.25 | 12.21 | 12.38 | 13.15 | 14.22 | 13.83 | 13.68 | 13.47 | 13.15 |
| 7 | 12.39 | 13.03 | 13.61 | 14.07 | 14.43 | 14.65 | 14.75 | 15.00 | 15.95 | 17.35 | 16.98 | 16.82 | 16.61 | 16.25 |
| 8 | 13.89 | 14.68 | 15.47 | 16.19 | 16.69 | 17.01 | 17.19 | 17.47 | 18.58 | 20.22 | 19.78 | 19.60 | 19.33 | 18.88 |
| 9 | 15.10 | 16.29 | 17.32 | 18.25 | 18.92 | 19.37 | 19.63 | 19.96 | 21.23 | 23.11 | 22.63 | 22.42 | 22.11 | 21.56 |
| 10 | ≈ 16.41 | 17.79 | 19.08 | 20.24 | 21.09 | 21.68 | 22.04 | 22.46 | 23.90 | 26.02 | 25.52 | 25.28 | 24.92 | 24.28 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.517 |
| SC2 | 0 | 8 | 17.469 |
| SC3 | -18 | 7 | 14.229 |
| SC4 | -25 | 6 | 11.582 |
| SC5 | -34 | 6 | 10.860 |
| A | 2857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.