EB-345AE6-B01 C
22.65 kW
Defrost: None
Product code: EB-445AC6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 20,426 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 55.5 m² |
| Inner volume | 13.7 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 128 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EB-445AC6-B01 C | None |
|---|---|
| EB-445AC6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.21 | 8.30 | 8.38 | 8.44 | 8.42 | 8.34 | 8.23 | 8.35 | 8.82 | 9.50 | 9.21 | 9.11 | 8.96 | 8.74 |
| 5 | 10.83 | 11.17 | 11.50 | 11.78 | 11.90 | 11.90 | 11.81 | 11.98 | 12.72 | 13.75 | 13.37 | 13.24 | 13.05 | 12.78 |
| 6 | 12.97 | 13.55 | 14.08 | 14.55 | 14.86 | 15.04 | 15.11 | 15.37 | 16.35 | 17.76 | 17.40 | 17.26 | 17.06 | 16.76 |
| 7 | 15.08 | 15.91 | 16.67 | 17.34 | 17.79 | 18.04 | 18.19 | 18.49 | 19.66 | 21.37 | 20.92 | 20.75 | 20.49 | 20.07 |
| 8 | 16.94 | 18.07 | 19.12 | 20.04 | 20.68 | 21.10 | 21.33 | 21.62 | 22.98 | 25.00 | 24.49 | 24.29 | 23.97 | 23.44 |
| 9 | 18.63 | 20.10 | 21.46 | 22.67 | 23.40 | 24.00 | 24.36 | 24.79 | 26.39 | 28.73 | 28.17 | 27.93 | 27.54 | 26.89 |
| 10 | ≈ 20.16 | 21.98 | 23.46 | 25.01 | 26.14 | 26.94 | 27.45 | 27.98 | 29.79 | 32.46 | 31.88 | 31.60 | 31.17 | 30.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 31.877 |
| SC2 | 0 | 8 | 21.618 |
| SC3 | -18 | 7 | 17.544 |
| SC4 | -25 | 6 | 14.075 |
| SC5 | -34 | 6 | 13.109 |
| A | 2967 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2967 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.