EA-250AE4-C10 C
25.63 kW
Defrost: None
Product code: EA-540AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,655 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 81.5 m² |
| Inner volume | 30.8 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 152 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-540AE8-C01 C | None |
|---|---|
| EA-540AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.53 | 9.52 | 9.54 | 9.57 | 9.54 | 9.45 | 9.33 | 9.58 | 10.19 | 11.00 | 10.72 | 10.62 | 10.47 | 10.25 |
| 5 | 12.53 | 12.71 | 12.88 | 13.04 | 13.08 | 13.01 | 12.87 | 13.10 | 13.92 | 15.07 | 14.66 | 14.52 | 14.34 | 14.08 |
| 6 | 15.49 | 15.91 | 16.31 | 16.61 | 16.77 | 16.78 | 16.65 | 16.87 | 17.90 | 19.37 | 18.76 | 18.54 | 18.22 | 17.73 |
| 7 | 18.20 | 18.94 | 19.62 | 20.21 | 20.54 | 20.66 | 20.57 | 20.80 | 22.06 | 23.89 | 23.15 | 22.85 | 22.42 | 21.70 |
| 8 | 20.58 | 21.59 | 22.53 | 23.37 | 23.84 | 24.17 | 24.30 | 24.64 | 26.17 | 28.43 | 27.65 | 27.29 | 26.76 | 25.87 |
| 9 | 22.73 | 24.08 | 25.19 | 26.29 | 27.03 | 27.50 | 27.72 | 28.13 | 29.88 | 32.44 | 31.67 | 31.32 | 30.79 | 29.88 |
| 10 | 24.71 | 26.28 | 27.84 | 29.20 | 30.19 | 30.82 | 31.14 | 31.63 | 33.61 | 36.49 | 35.66 | 35.26 | 34.65 | 33.59 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 35.658 |
| SC2 | 0 | 8 | 24.640 |
| SC3 | -18 | 7 | 20.368 |
| SC4 | -25 | 6 | 16.305 |
| SC5 | -34 | 6 | 15.604 |
| A | 3117 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 3117 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.