EB-330AB7-B01 C
4.56 kW
Defrost: None
Product code: EB-330AB6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,722 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 13.4 m² |
| Inner volume | 3.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 36 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | E |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AB6-B05 C | None |
|---|---|
| EB-330AB6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.67 | 1.63 | 1.61 | 1.61 | 1.59 | 1.58 | 1.57 | 1.59 | 1.69 | 1.82 | 1.78 | 1.77 | 1.75 | 1.72 |
| 5 | 2.25 | 2.23 | 2.22 | 2.22 | 2.21 | 2.19 | 2.16 | 2.19 | 2.32 | 2.51 | 2.45 | 2.43 | 2.40 | 2.36 |
| 6 | 2.85 | 2.85 | 2.87 | 2.89 | 2.88 | 2.87 | 2.84 | 2.86 | 3.03 | 3.27 | 3.17 | 3.14 | 3.10 | 3.03 |
| 7 | 3.44 | 3.48 | 3.53 | 3.57 | 3.59 | 3.59 | 3.56 | 3.58 | 3.79 | 4.09 | 3.97 | 3.92 | 3.85 | 3.75 |
| 8 | 3.96 | 4.05 | 4.14 | 4.23 | 4.29 | 4.32 | 4.31 | 4.34 | 4.59 | 4.97 | 4.82 | 4.76 | 4.67 | 4.54 |
| 9 | 4.47 | 4.57 | 4.70 | 4.83 | 4.91 | 4.96 | 4.98 | 5.03 | 5.34 | 5.79 | 5.66 | 5.60 | 5.52 | 5.37 |
| 10 | 4.94 | 5.11 | 5.27 | 5.43 | 5.53 | 5.60 | 5.63 | 5.69 | 6.04 | 6.55 | 6.40 | 6.34 | 6.24 | 6.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.403 |
| SC2 | 0 | 8 | 4.336 |
| SC3 | -18 | 7 | 3.584 |
| SC4 | -25 | 6 | 2.867 |
| SC5 | -34 | 6 | 2.856 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.