EA-DR-245EA10-A07 C
7.60 kW
Defrost: None
Product code: EA-DR-245BB10-A07 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,760 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 31.9 m² |
| Inner volume | 12.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 107 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 960 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.4 dB(A) |
| Energy class | E |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-DR-245BB10-A07 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | 3.30 | 3.40 | 3.45 | 3.47 | 3.47 | 3.49 | 3.70 | 4.00 | 3.89 | 3.85 | 3.79 | 3.69 |
| 5 | 3.80 | 4.06 | 4.26 | 4.46 | 4.60 | 4.68 | 4.72 | 4.78 | 5.07 | 5.50 | 5.38 | 5.33 | 5.25 | 5.14 |
| 6 | 4.47 | 4.80 | 5.14 | 5.44 | 5.67 | 5.83 | 5.94 | 6.05 | 6.44 | 7.02 | 6.91 | 6.87 | 6.79 | 6.65 |
| 7 | ≈ 4.98 | 5.46 | 5.91 | 6.32 | 6.63 | 6.87 | 7.03 | 7.18 | 7.66 | 8.35 | 8.24 | 8.19 | 8.11 | 7.98 |
| 8 | ≈ 4.40 | ≈ 6.05 | 6.62 | 7.15 | 7.56 | 7.88 | 8.11 | 8.30 | 8.86 | 9.69 | 9.57 | 9.52 | 9.44 | 9.29 |
| 9 | ≈ 2.92 | ≈ 6.59 | 7.28 | 7.93 | 8.46 | 8.86 | 9.17 | 9.42 | 10.06 | 11.01 | 10.91 | 10.86 | 10.77 | 10.61 |
| 10 | ≈ 2.23 | ≈ 7.08 | 7.89 | 8.67 | 9.31 | 9.81 | 10.20 | 10.51 | 11.25 | 12.33 | 12.24 | 12.19 | 12.10 | 11.93 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | 3.00 | 3.06 | 3.10 | 3.11 | 3.11 | 3.14 | 3.32 | 3.59 | 3.50 | 3.47 | 3.41 | 3.34 |
| 5 | 3.53 | 3.73 | 3.91 | 4.06 | 4.14 | 4.19 | 4.22 | 4.26 | 4.52 | 4.90 | 4.79 | 4.74 | 4.68 | 4.58 |
| 6 | 4.18 | 4.45 | 4.74 | 4.99 | 5.16 | 5.28 | 5.35 | 5.42 | 5.77 | 6.26 | 6.13 | 6.08 | 6.00 | 5.87 |
| 7 | ≈ 4.70 | 5.10 | 5.48 | 5.81 | 6.06 | 6.24 | 6.37 | 6.49 | 6.91 | 7.54 | 7.42 | 7.37 | 7.30 | 7.17 |
| 8 | ≈ 5.17 | 5.68 | 6.16 | 6.59 | 6.93 | 7.18 | 7.35 | 7.50 | 8.00 | 8.73 | 8.61 | 8.56 | 8.48 | 8.33 |
| 9 | ≈ 4.46 | ≈ 6.21 | 6.80 | 7.34 | 7.76 | 8.08 | 8.32 | 8.52 | 9.09 | 9.93 | 9.81 | 9.75 | 9.66 | 9.50 |
| 10 | ≈ 2.91 | ≈ 6.68 | 7.39 | 8.04 | 8.56 | 8.97 | 9.27 | 9.52 | 10.17 | 11.12 | 11.01 | 10.95 | 10.85 | 10.67 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 12.240 | 11.007 |
| SC2 | 0 | 8 | 8.303 | 7.504 |
| SC3 | -18 | 7 | 6.454 | 5.920 |
| SC4 | -25 | 6 | 5.138 | 4.736 |
| SC5 | -34 | 6 | 4.473 | 4.249 |
| A | 1867 mm |
|---|---|
| B | 700 mm |
| C | 775 mm |
| F | 660 mm |
| E1 | 768 mm |
| E | 1535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1867 mm |
|---|---|
| Width | 700 mm |
| Height | 775 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.