EA-DR-245BB10-A07 C
8.61 kW
Defrost: None
Product code: EA-DR-245EA10-A07 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,534 m³/h |
|---|---|
| Air throw | 24 m |
| External surface | 29.3 m² |
| Inner volume | 11.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 115 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 960 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.1 dB(A) |
| Energy class | E |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-DR-245EA10-A07 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | 2.98 | 3.02 | 3.03 | 3.03 | 3.03 | 3.21 | 3.47 | 3.38 | 3.35 | 3.30 | 3.23 |
| 5 | 3.50 | 3.68 | 3.83 | 3.96 | 4.05 | 4.08 | 4.10 | 4.12 | 4.37 | 4.74 | 4.63 | 4.58 | 4.52 | 4.42 |
| 6 | 4.16 | 4.41 | 4.66 | 4.88 | 5.03 | 5.14 | 5.20 | 5.26 | 5.59 | 6.06 | 5.94 | 5.89 | 5.82 | 5.70 |
| 7 | 4.70 | 5.07 | 5.40 | 5.71 | 5.93 | 6.10 | 6.22 | 6.32 | 6.73 | 7.34 | 7.23 | 7.19 | 7.12 | 7.00 |
| 8 | ≈ 5.19 | 5.66 | 6.09 | 6.49 | 6.79 | 7.02 | 7.19 | 7.32 | 7.80 | 8.51 | 8.40 | 8.36 | 8.28 | 8.15 |
| 9 | ≈ 5.63 | 6.20 | 6.74 | 7.23 | 7.62 | 7.92 | 8.14 | 8.31 | 8.87 | 9.69 | 9.58 | 9.53 | 9.45 | 9.31 |
| 10 | ≈ 4.17 | ≈ 6.69 | 7.34 | 7.94 | 8.42 | 8.79 | 9.08 | 9.30 | 9.93 | 10.86 | 10.76 | 10.71 | 10.63 | 10.48 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | 2.70 | 2.72 | 2.73 | 2.73 | 2.74 | 2.90 | 3.14 | 3.06 | 3.03 | 2.99 | 2.93 |
| 5 | 3.24 | 3.37 | 3.48 | 3.58 | 3.64 | 3.68 | 3.69 | 3.71 | 3.93 | 4.25 | 4.15 | 4.11 | 4.06 | 3.97 |
| 6 | 3.87 | 4.09 | 4.26 | 4.43 | 4.54 | 4.62 | 4.66 | 4.70 | 4.99 | 5.42 | 5.30 | 5.26 | 5.19 | 5.08 |
| 7 | 4.44 | 4.72 | 4.99 | 5.24 | 5.42 | 5.55 | 5.65 | 5.72 | 6.08 | 6.61 | 6.49 | 6.44 | 6.36 | 6.24 |
| 8 | 4.90 | 5.29 | 5.64 | 5.97 | 6.21 | 6.39 | 6.53 | 6.63 | 7.07 | 7.70 | 7.60 | 7.55 | 7.48 | 7.35 |
| 9 | ≈ 5.33 | 5.81 | 6.26 | 6.67 | 6.98 | 7.22 | 7.40 | 7.54 | 8.03 | 8.77 | 8.66 | 8.61 | 8.53 | 8.39 |
| 10 | ≈ 5.72 | 6.29 | 6.84 | 7.34 | 7.73 | 8.03 | 8.26 | 8.43 | 9.00 | 9.83 | 9.72 | 9.67 | 9.59 | 9.44 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 10.759 | 9.718 |
| SC2 | 0 | 8 | 7.321 | 6.634 |
| SC3 | -18 | 7 | 5.805 | 5.316 |
| SC4 | -25 | 6 | 4.655 | 4.255 |
| SC5 | -34 | 6 | 4.226 | 3.923 |
| A | 2167 mm |
|---|---|
| B | 650 mm |
| C | 875 mm |
| F | 610 mm |
| E1 | 918 mm |
| E | 1835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2167 mm |
|---|---|
| Width | 650 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.