EA-230BC10-C05 C
3.52 kW
Defrost: Electric
Product code: EA-135AC6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,408 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 11.0 m² |
| Inner volume | 3.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-135AC6-C01 C | None |
|---|---|
| EA-135AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.25 | 1.24 | 1.23 | 1.23 | 1.23 | 1.21 | 1.20 | 1.22 | 1.29 | 1.40 | 1.36 | 1.35 | 1.34 | 1.31 |
| 5 | 1.67 | 1.68 | 1.69 | 1.70 | 1.70 | 1.69 | 1.67 | 1.69 | 1.79 | 1.94 | 1.89 | 1.87 | 1.85 | 1.81 |
| 6 | 2.09 | 2.13 | 2.17 | 2.21 | 2.22 | 2.21 | 2.19 | 2.21 | 2.35 | 2.53 | 2.46 | 2.43 | 2.40 | 2.34 |
| 7 | 2.49 | 2.58 | 2.66 | 2.72 | 2.76 | 2.76 | 2.75 | 2.77 | 2.94 | 3.17 | 3.07 | 3.04 | 2.98 | 2.90 |
| 8 | 2.84 | 2.97 | 3.09 | 3.19 | 3.26 | 3.30 | 3.31 | 3.35 | 3.55 | 3.84 | 3.73 | 3.68 | 3.61 | 3.50 |
| 9 | 3.15 | 3.32 | 3.49 | 3.61 | 3.71 | 3.77 | 3.80 | 3.85 | 4.09 | 4.44 | 4.34 | 4.29 | 4.23 | 4.12 |
| 10 | 3.43 | 3.66 | 3.84 | 4.03 | 4.16 | 4.24 | 4.28 | 4.34 | 4.61 | 5.01 | 4.90 | 4.85 | 4.78 | 4.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.900 |
| SC2 | 0 | 8 | 3.347 |
| SC3 | -18 | 7 | 2.741 |
| SC4 | -25 | 6 | 2.170 |
| SC5 | -34 | 6 | 2.106 |
| A | 857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.