EA-240AC6-C01 C
9.25 kW
Defrost: None
Product code: EA-235AG7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,910 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 38.2 m² |
| Inner volume | 12.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 68 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-235AG7-C01 C | None |
|---|---|
| EA-235AG7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.62 | 3.62 | 3.64 | 3.66 | 3.66 | 3.63 | 3.59 | 3.70 | 3.95 | 4.29 | 4.21 | 4.18 | 4.15 | 4.10 |
| 5 | 4.70 | 4.75 | 4.82 | 4.88 | 4.89 | 4.87 | 4.81 | 4.91 | 5.22 | 5.66 | 5.50 | 5.45 | 5.37 | 5.27 |
| 6 | 5.73 | 5.87 | 6.00 | 6.12 | 6.17 | 6.16 | 6.10 | 6.18 | 6.56 | 7.10 | 6.86 | 6.77 | 6.64 | 6.44 |
| 7 | 6.75 | 6.98 | 7.20 | 7.37 | 7.47 | 7.49 | 7.44 | 7.51 | 7.95 | 8.60 | 8.30 | 8.18 | 8.00 | 7.70 |
| 8 | 7.68 | 8.02 | 8.34 | 8.61 | 8.78 | 8.83 | 8.78 | 8.86 | 9.38 | 10.14 | 9.80 | 9.65 | 9.42 | 9.04 |
| 9 | 8.50 | 8.96 | 9.37 | 9.74 | 9.98 | 10.10 | 10.10 | 10.22 | 10.82 | 11.68 | 11.31 | 11.14 | 10.87 | 10.41 |
| 10 | 9.25 | 9.83 | 10.36 | 10.78 | 11.09 | 11.26 | 11.32 | 11.46 | 12.15 | 13.14 | 12.78 | 12.60 | 12.33 | 11.80 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.781 |
| SC2 | 0 | 8 | 8.863 |
| SC3 | -18 | 7 | 7.417 |
| SC4 | -25 | 6 | 6.003 |
| SC5 | -34 | 6 | 5.769 |
| A | 1357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.