EA-340AG6-C01 C
18.66 kW
Defrost: Electric
Product code: EA-245AE4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,698 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 79.9 m² |
| Inner volume | 17.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 97 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EA-245AE4-C01 C | None |
|---|---|
| EA-245AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.10 | 7.14 | 7.19 | 7.25 | 7.25 | 7.21 | 7.14 | 7.36 | 7.85 | 8.52 | 8.36 | 8.29 | 8.20 | 8.07 |
| 5 | 9.24 | 9.44 | 9.63 | 9.78 | 9.83 | 9.80 | 9.70 | 9.89 | 10.52 | 11.40 | 11.11 | 11.01 | 10.89 | 10.72 |
| 6 | 11.35 | 11.76 | 12.13 | 12.43 | 12.57 | 12.57 | 12.47 | 12.64 | 13.41 | 14.51 | 14.06 | 13.89 | 13.65 | 13.28 |
| 7 | 13.15 | 13.76 | 14.32 | 14.81 | 15.11 | 15.21 | 15.24 | 15.46 | 16.43 | 17.80 | 17.22 | 16.99 | 16.64 | 16.06 |
| 8 | 14.75 | 15.61 | 16.29 | 16.96 | 17.40 | 17.64 | 17.70 | 17.95 | 19.06 | 20.68 | 20.10 | 19.85 | 19.47 | 18.83 |
| 9 | 16.23 | 17.24 | 18.24 | 19.11 | 19.71 | 20.05 | 20.18 | 20.46 | 21.72 | 23.55 | 22.89 | 22.58 | 22.12 | 21.34 |
| 10 | 17.37 | 18.84 | 20.10 | 21.21 | 21.97 | 22.45 | 22.66 | 23.00 | 24.41 | 26.45 | 25.72 | 25.37 | 24.83 | 23.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.722 |
| SC2 | 0 | 8 | 17.949 |
| SC3 | -18 | 7 | 14.949 |
| SC4 | -25 | 6 | 12.130 |
| SC5 | -34 | 6 | 11.455 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.