EA-163GD10-C08 C
17.80 kW
Defrost: None
Product code: EA-250AC6-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,861 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 49.7 m² |
| Inner volume | 14.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 97 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.2 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-250AC6-C09 C | None |
|---|---|
| EA-250AC6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.41 | 6.41 | 6.41 | 6.41 | 6.37 | 6.31 | 6.23 | 6.27 | 6.62 | 7.14 | 6.94 | 6.86 | 6.76 | 6.61 |
| 5 | 8.60 | 8.75 | 8.85 | 8.96 | 8.99 | 8.94 | 8.85 | 8.91 | 9.44 | 10.19 | 9.90 | 9.79 | 9.65 | 9.41 |
| 6 | 10.64 | 11.01 | 11.35 | 11.64 | 11.78 | 11.82 | 11.75 | 11.84 | 12.55 | 13.55 | 13.15 | 13.01 | 12.80 | 12.48 |
| 7 | 12.32 | 12.89 | 13.41 | 13.81 | 14.12 | 14.32 | 14.42 | 14.61 | 15.53 | 16.86 | 16.51 | 16.37 | 16.17 | 15.79 |
| 8 | 13.87 | 14.59 | 15.31 | 15.96 | 16.41 | 16.70 | 16.87 | 17.10 | 18.19 | 19.77 | 19.36 | 19.20 | 18.96 | 18.56 |
| 9 | 15.16 | 16.25 | 17.20 | 18.06 | 18.67 | 19.09 | 19.34 | 19.63 | 20.88 | 22.71 | 22.27 | 22.08 | 21.80 | 21.30 |
| 10 | 16.50 | 17.80 | 19.01 | 20.09 | 20.89 | 21.45 | 21.81 | 22.17 | 23.59 | 25.68 | 25.21 | 25.01 | 24.67 | 24.10 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.214 |
| SC2 | 0 | 8 | 17.104 |
| SC3 | -18 | 7 | 13.948 |
| SC4 | -25 | 6 | 11.346 |
| SC5 | -34 | 6 | 10.734 |
| A | 2087 mm |
|---|---|
| B | 590 mm |
| C | 685 mm |
| F | 395 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2087 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.