EA-440AC8-C01 C
15.42 kW
Defrost: Electric
Product code: EA-340AC4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,010 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 58.6 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 85 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-340AC4-C01 C | None |
|---|---|
| EA-340AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.74 | 5.75 | 5.78 | 5.81 | 5.80 | 5.76 | 5.71 | 5.85 | 6.20 | 6.71 | 6.56 | 6.50 | 6.43 | 6.31 |
| 5 | 7.60 | 7.75 | 7.85 | 7.97 | 8.00 | 7.96 | 7.88 | 8.03 | 8.53 | 9.23 | 9.00 | 8.92 | 8.81 | 8.66 |
| 6 | 9.36 | 9.68 | 9.98 | 10.24 | 10.36 | 10.36 | 10.27 | 10.42 | 11.06 | 11.96 | 11.60 | 11.47 | 11.28 | 11.01 |
| 7 | 10.81 | 11.31 | 11.76 | 12.10 | 12.35 | 12.49 | 12.52 | 12.72 | 13.52 | 14.69 | 14.33 | 14.20 | 13.99 | 13.59 |
| 8 | 12.16 | 12.78 | 13.41 | 13.95 | 14.32 | 14.53 | 14.61 | 14.82 | 15.75 | 17.11 | 16.68 | 16.51 | 16.26 | 15.84 |
| 9 | 13.27 | 14.22 | 15.05 | 15.77 | 16.27 | 16.57 | 16.71 | 16.95 | 18.01 | 19.56 | 19.08 | 18.88 | 18.57 | 18.05 |
| 10 | 14.44 | 15.57 | 16.61 | 17.54 | 18.18 | 18.59 | 18.80 | 19.10 | 20.29 | 22.04 | 21.52 | 21.29 | 20.93 | 20.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.523 |
| SC2 | 0 | 8 | 14.820 |
| SC3 | -18 | 7 | 12.214 |
| SC4 | -25 | 6 | 9.977 |
| SC5 | -34 | 6 | 9.440 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.