Skip to Content

Unit cooler EA-630BC4-C01 C ED

Defrost: Electric

Unit cooler EA-630BC4-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-630BC4-C01 C ED

Cooling capacity i
13.83 kW
Air flow
6,892 m³/h
Fin spacing
4.2 mm
Air throw
8 m
Fans
6 × ⌀300 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 6 — Number of fans (one digit).
  • C
    Fan diameter: 30 — Ø300 mm
  • D
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole; Ø630: 230V/1Ph/50Hz, 6-pole; Ø800: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 6,892 m³/h
Air throw 8 m
External surface 55.8 m²
Inner volume 11.8 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 80 kg
Fans
Quantity 6
Diameter 300 mm
Speed 1,380 rpm
Power 372 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 51.0 dB(A)
Sound power 73.4 dB(A)
Energy class C
Connections
Inlet Ø22
Outlet Ø28
Defrost
EA-630BC4-C01 C None
EA-630BC4-C01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
13.330 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 5.09 5.30 5.48 5.63 5.72 5.75 5.73 5.90 6.29 6.83 6.71 6.67 6.62 6.52
5 6.46 6.83 7.16 7.45 7.65 7.74 7.75 7.89 8.40 9.14 8.93 8.85 8.74 8.58
6 7.58 8.10 8.51 8.95 9.25 9.44 9.54 9.74 10.38 11.31 11.08 10.99 10.86 10.63
7 8.57 9.20 9.85 10.43 10.86 11.14 11.30 11.53 12.28 13.38 13.11 12.99 12.81 12.51
8 ≈ 9.19 10.27 11.10 11.86 12.43 12.82 13.04 13.33 14.20 15.47 15.17 15.03 14.81 14.41
9 ≈ 10.17 11.24 12.27 13.22 13.94 14.45 14.78 15.13 16.12 17.57 17.25 17.09 16.83 16.34
10 ≈ 7.79 ≈ 12.12 13.36 14.50 15.39 16.05 16.49 16.92 18.03 19.67 19.34 19.16 18.87 18.29

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 19.340
SC2 0 8 13.330
SC3 -18 7 10.620
SC4 -25 6 8.514
SC5 -34 6 7.696

Dimensions

Dimension drawing of EA-630BC4-C01 C
Dimension drawing
Dimensions as drawn
A 2557 mm
B 523 mm
C 445 mm
F 345 mm
E1 385 mm
E2 367 mm
E 2235 mm
D IN 1 x Ø22
D OUT 1 x Ø28
Overall [mm]
Length 2557 mm
Width 523 mm
Height 445 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.