EB-330AC7-B01 C
5.64 kW
Defrost: None
Product code: EB-140AC4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,342 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 19.1 m² |
| Inner volume | 3.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-140AC4-B01 C | None |
|---|---|
| EB-140AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.11 | 2.14 | 2.17 | 2.19 | 2.20 | 2.20 | 2.19 | 2.22 | 2.37 | 2.56 | 2.51 | 2.48 | 2.45 | 2.41 |
| 5 | 2.74 | 2.83 | 2.91 | 2.98 | 3.01 | 3.03 | 3.02 | 3.05 | 3.24 | 3.51 | 3.43 | 3.40 | 3.35 | 3.29 |
| 6 | 3.30 | 3.44 | 3.58 | 3.70 | 3.78 | 3.84 | 3.86 | 3.92 | 4.17 | 4.53 | 4.43 | 4.39 | 4.33 | 4.23 |
| 7 | 3.82 | 4.03 | 4.22 | 4.37 | 4.49 | 4.57 | 4.61 | 4.68 | 4.98 | 5.41 | 5.30 | 5.26 | 5.19 | 5.08 |
| 8 | 4.28 | 4.57 | 4.82 | 5.05 | 5.21 | 5.32 | 5.37 | 5.45 | 5.80 | 6.31 | 6.18 | 6.12 | 6.04 | 5.90 |
| 9 | 4.71 | 5.07 | 5.40 | 5.70 | 5.91 | 6.06 | 6.12 | 6.22 | 6.62 | 7.19 | 7.06 | 6.99 | 6.90 | 6.74 |
| 10 | ≈ 5.09 | 5.54 | 5.96 | 6.33 | 6.56 | 6.75 | 6.87 | 7.00 | 7.45 | 8.11 | 7.96 | 7.89 | 7.78 | 7.60 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.960 |
| SC2 | 0 | 8 | 5.451 |
| SC3 | -18 | 7 | 4.427 |
| SC4 | -25 | 6 | 3.579 |
| SC5 | -34 | 6 | 3.332 |
| A | 1017 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1017 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.