EB-225AC7-B05 C
2.63 kW
Defrost: Electric
Product code: EB-320AB4-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,313 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 13.5 m² |
| Inner volume | 2.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 3 |
|---|---|
| Diameter | 200 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 60.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EB-320AB4-C05 C | None |
|---|---|
| EB-320AB4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.02 | 1.03 | 1.04 | 1.05 | 1.06 | 1.07 | 1.07 | 1.08 | 1.15 | 1.25 | 1.23 | 1.22 | 1.21 | 1.20 |
| 5 | 1.31 | 1.33 | 1.36 | 1.38 | 1.40 | 1.41 | 1.42 | 1.43 | 1.52 | 1.65 | 1.62 | 1.61 | 1.59 | 1.56 |
| 6 | 1.59 | 1.63 | 1.68 | 1.72 | 1.75 | 1.77 | 1.78 | 1.80 | 1.91 | 2.08 | 2.03 | 2.02 | 1.99 | 1.95 |
| 7 | 1.85 | 1.92 | 1.99 | 2.06 | 2.10 | 2.14 | 2.16 | 2.18 | 2.32 | 2.52 | 2.47 | 2.45 | 2.41 | 2.36 |
| 8 | 2.08 | 2.18 | 2.27 | 2.36 | 2.42 | 2.47 | 2.50 | 2.54 | 2.70 | 2.94 | 2.89 | 2.87 | 2.83 | 2.78 |
| 9 | 2.32 | 2.44 | 2.56 | 2.66 | 2.74 | 2.80 | 2.84 | 2.88 | 3.07 | 3.34 | 3.29 | 3.26 | 3.22 | 3.16 |
| 10 | 2.52 | 2.68 | 2.83 | 2.96 | 3.06 | 3.14 | 3.18 | 3.23 | 3.44 | 3.75 | 3.69 | 3.66 | 3.62 | 3.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.687 |
| SC2 | 0 | 8 | 2.536 |
| SC3 | -18 | 7 | 2.076 |
| SC4 | -25 | 6 | 1.678 |
| SC5 | -34 | 6 | 1.598 |
| A | 1457 mm |
|---|---|
| B | 490 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 384 mm |
| E2 | 367 mm |
| E | 1135 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1457 mm |
|---|---|
| Width | 490 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.