EB-145AE4-B01 C
8.45 kW
Defrost: None
Product code: EB-430AC4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,312 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 33.0 m² |
| Inner volume | 5.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EB-430AC4-B05 C | None |
|---|---|
| EB-430AC4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.27 | 3.30 | 3.35 | 3.39 | 3.40 | 3.40 | 3.38 | 3.48 | 3.71 | 4.03 | 3.96 | 3.94 | 3.91 | 3.86 |
| 5 | 4.22 | 4.33 | 4.43 | 4.53 | 4.57 | 4.58 | 4.55 | 4.65 | 4.95 | 5.37 | 5.23 | 5.19 | 5.13 | 5.04 |
| 6 | 5.10 | 5.29 | 5.47 | 5.63 | 5.74 | 5.80 | 5.80 | 5.89 | 6.26 | 6.79 | 6.60 | 6.53 | 6.43 | 6.26 |
| 7 | 5.87 | 6.15 | 6.41 | 6.64 | 6.79 | 6.88 | 6.91 | 7.02 | 7.46 | 8.11 | 7.91 | 7.83 | 7.71 | 7.51 |
| 8 | 6.65 | 7.02 | 7.36 | 7.66 | 7.86 | 7.97 | 8.01 | 8.14 | 8.64 | 9.39 | 9.16 | 9.06 | 8.91 | 8.65 |
| 9 | 7.33 | 7.81 | 8.25 | 8.64 | 8.90 | 9.07 | 9.14 | 9.27 | 9.84 | 10.67 | 10.42 | 10.30 | 10.12 | 9.81 |
| 10 | 7.95 | 8.55 | 9.10 | 9.59 | 9.93 | 10.11 | 10.22 | 10.39 | 11.04 | 11.98 | 11.70 | 11.57 | 11.36 | 11.00 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.698 |
| SC2 | 0 | 8 | 8.137 |
| SC3 | -18 | 7 | 6.709 |
| SC4 | -25 | 6 | 5.466 |
| SC5 | -34 | 6 | 5.145 |
| A | 2037 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.