EB-145AE6-B01 C
7.43 kW
Defrost: Electric
Product code: EB-430AC6-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,578 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 23.9 m² |
| Inner volume | 5.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EB-430AC6-B05 C | None |
|---|---|
| EB-430AC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.81 | 2.81 | 2.82 | 2.84 | 2.84 | 2.83 | 2.80 | 2.87 | 3.06 | 3.31 | 3.25 | 3.22 | 3.18 | 3.13 |
| 5 | 3.69 | 3.74 | 3.79 | 3.85 | 3.87 | 3.86 | 3.83 | 3.90 | 4.14 | 4.49 | 4.37 | 4.33 | 4.28 | 4.21 |
| 6 | 4.54 | 4.66 | 4.78 | 4.88 | 4.94 | 4.96 | 4.94 | 5.00 | 5.30 | 5.74 | 5.58 | 5.52 | 5.43 | 5.30 |
| 7 | 5.29 | 5.48 | 5.67 | 5.84 | 5.96 | 6.03 | 6.05 | 6.14 | 6.53 | 7.08 | 6.88 | 6.80 | 6.68 | 6.49 |
| 8 | 6.03 | 6.29 | 6.51 | 6.74 | 6.90 | 7.00 | 7.05 | 7.14 | 7.59 | 8.25 | 8.06 | 7.98 | 7.85 | 7.64 |
| 9 | 6.68 | 7.03 | 7.36 | 7.66 | 7.86 | 7.98 | 8.04 | 8.16 | 8.67 | 9.42 | 9.21 | 9.11 | 8.96 | 8.70 |
| 10 | 7.29 | 7.74 | 8.16 | 8.53 | 8.79 | 8.96 | 9.05 | 9.18 | 9.76 | 10.60 | 10.37 | 10.24 | 10.07 | 9.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.367 |
| SC2 | 0 | 8 | 7.142 |
| SC3 | -18 | 7 | 5.893 |
| SC4 | -25 | 6 | 4.775 |
| SC5 | -34 | 6 | 4.569 |
| A | 2037 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.