ED-DP-240AC7-B22 C
8.12 kW
Defrost: None
Product code: ED-DP-235AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,806 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 54.8 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 92 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 63.0 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-235AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.21 | 3.33 | 3.45 | 3.56 | 3.62 | 3.65 | 3.65 | 3.75 | 4.00 | 4.35 | 4.27 | 4.23 | 4.19 | 4.13 |
| 5 | 3.95 | 4.16 | 4.36 | 4.53 | 4.64 | 4.69 | 4.70 | 4.79 | 5.10 | 5.55 | 5.41 | 5.35 | 5.27 | 5.13 |
| 6 | 4.67 | 4.97 | 5.25 | 5.49 | 5.66 | 5.74 | 5.77 | 5.86 | 6.23 | 6.77 | 6.59 | 6.52 | 6.40 | 6.19 |
| 7 | 5.29 | 5.69 | 6.06 | 6.39 | 6.62 | 6.73 | 6.80 | 6.91 | 7.35 | 7.98 | 7.78 | 7.69 | 7.54 | 7.28 |
| 8 | ≈ 5.84 | 6.34 | 6.82 | 7.18 | 7.49 | 7.68 | 7.79 | 7.92 | 8.42 | 9.14 | 8.93 | 8.83 | 8.67 | 8.37 |
| 9 | 6.32 | 6.94 | 7.46 | 7.98 | 8.36 | 8.62 | 8.76 | 8.92 | 9.48 | 10.30 | 10.07 | 9.95 | 9.77 | 9.43 |
| 10 | 6.74 | 7.33 | 8.11 | 8.73 | 9.21 | 9.54 | 9.73 | 9.92 | 10.55 | 11.46 | 11.22 | 11.09 | 10.88 | 10.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.216 |
| SC2 | 0 | 8 | 7.919 |
| SC3 | -18 | 7 | 6.493 |
| SC4 | -25 | 6 | 5.250 |
| SC5 | -34 | 6 | 4.742 |
| A | 1548 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.