Skip to Content

Unit cooler ED-145AC7-C23 C

Unit cooler ED-145AC7-C23 C
Illustrative photo

Producer: Karyer · Line: ED (General)

Product code: ED-145AC7-C23 C

Cooling capacity i
6.70 kW
Air flow
4,897 m³/h
Fin spacing
7.0 mm
Air throw
9 m
Fans
1 × ⌀450 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED — ED - double-flow ceiling unit cooler
  • B
    Number of fans: 1 — Number of fans (one digit).
  • C
    Fan diameter: 45 — Ø450 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 7 — Fin spacing about 7 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 23 — Ø450: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 4,897 m³/h
Air throw 9 m
External surface 20.3 m²
Inner volume 7.3 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 61 kg
Fans
Quantity 1
Diameter 450 mm
Speed 1,300 rpm
Power 350 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 80.0 dB(A)
Energy class C
Connections
Inlet Ø12,7
Outlet Ø28
Defrost
ED-145AC7-C23 C None
ED-145AC7-C23 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
6.392 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 2.39 2.36 2.34 2.33 2.31 2.29 2.27 2.28 2.41 2.60 2.53 2.51 2.48 2.43
5 3.22 3.22 3.23 3.24 3.23 3.20 3.17 3.18 3.36 3.63 3.53 3.49 3.44 3.37
6 4.04 4.10 4.15 4.21 4.22 4.21 4.17 4.18 4.43 4.78 4.63 4.58 4.51 4.40
7 4.84 4.98 5.10 5.21 5.25 5.27 5.25 5.26 5.57 6.02 5.84 5.77 5.67 5.51
8 5.56 5.77 5.97 6.15 6.28 6.36 6.36 6.39 6.77 7.32 7.12 7.04 6.92 6.72
9 6.18 6.48 6.75 7.00 7.14 7.26 7.33 7.41 7.87 8.55 8.38 8.30 8.19 7.99
10 6.76 7.15 7.47 7.79 8.02 8.17 8.27 8.37 8.90 9.67 9.48 9.40 9.28 9.07

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 9.482
SC2 0 8 6.392
SC3 -18 7 5.234
SC4 -25 6 4.154
SC5 -34 6 4.054

Dimensions

Dimension drawing of ED-145AC7-C23 C
Dimension drawing
Dimensions as drawn
A 1148 mm
B 1210 mm
C 365 mm
F 1135 mm
G 441 mm
E1 835 mm
D IN 1 x Ø12,7
D OUT 1 x Ø28
Overall [mm]
Length 1148 mm
Width 1210 mm
Height 441 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.