EA-163FD10-C19 C
13.05 kW
Defrost: None
Product code: EA-630BE6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,449 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 59.9 m² |
| Inner volume | 16.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 72 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-630BE6-C05 C | None |
|---|---|
| EA-630BE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.08 | 5.13 | 5.20 | 5.26 | 5.29 | 5.28 | 5.23 | 5.38 | 5.74 | 6.24 | 6.13 | 6.09 | 6.05 | 6.00 |
| 5 | 6.49 | 6.65 | 6.80 | 6.94 | 7.01 | 7.02 | 6.97 | 7.10 | 7.55 | 8.19 | 7.97 | 7.89 | 7.78 | 7.61 |
| 6 | 7.88 | 8.16 | 8.43 | 8.64 | 8.77 | 8.82 | 8.79 | 8.91 | 9.45 | 10.25 | 9.94 | 9.82 | 9.63 | 9.34 |
| 7 | 9.13 | 9.57 | 9.97 | 10.33 | 10.55 | 10.65 | 10.63 | 10.76 | 11.41 | 12.37 | 11.98 | 11.83 | 11.59 | 11.20 |
| 8 | 10.24 | 10.82 | 11.36 | 11.84 | 12.11 | 12.29 | 12.36 | 12.54 | 13.32 | 14.45 | 14.08 | 13.89 | 13.60 | 13.11 |
| 9 | 11.25 | 12.00 | 12.63 | 13.24 | 13.66 | 13.92 | 14.03 | 14.23 | 15.11 | 16.39 | 15.98 | 15.79 | 15.49 | 14.96 |
| 10 | 12.16 | 13.03 | 13.88 | 14.65 | 15.18 | 15.52 | 15.69 | 15.93 | 16.92 | 18.34 | 17.90 | 17.69 | 17.34 | 16.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.904 |
| SC2 | 0 | 8 | 12.541 |
| SC3 | -18 | 7 | 10.438 |
| SC4 | -25 | 6 | 8.427 |
| SC5 | -34 | 6 | 7.949 |
| A | 2557 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.