EB-430AC4-B01 C
9.10 kW
Defrost: Electric
Product code: EB-240AC7-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,005 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 24.2 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 62 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-240AC7-B01 C | None |
|---|---|
| EB-240AC7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.33 | 3.33 | 3.34 | 3.36 | 3.35 | 3.33 | 3.30 | 3.33 | 3.53 | 3.80 | 3.70 | 3.66 | 3.61 | 3.53 |
| 5 | 4.39 | 4.47 | 4.55 | 4.62 | 4.65 | 4.65 | 4.62 | 4.66 | 4.94 | 5.34 | 5.19 | 5.14 | 5.07 | 4.96 |
| 6 | 5.40 | 5.58 | 5.76 | 5.92 | 6.01 | 6.05 | 6.05 | 6.09 | 6.46 | 6.99 | 6.81 | 6.74 | 6.63 | 6.47 |
| 7 | 6.26 | 6.53 | 6.79 | 7.03 | 7.19 | 7.30 | 7.36 | 7.46 | 7.93 | 8.62 | 8.45 | 8.38 | 8.28 | 8.11 |
| 8 | 7.12 | 7.48 | 7.83 | 8.14 | 8.35 | 8.50 | 8.60 | 8.71 | 9.27 | 10.08 | 9.88 | 9.80 | 9.68 | 9.47 |
| 9 | 7.87 | 8.36 | 8.81 | 9.22 | 9.52 | 9.72 | 9.84 | 9.98 | 10.62 | 11.55 | 11.34 | 11.25 | 11.09 | 10.86 |
| 10 | 8.56 | 9.18 | 9.75 | 10.27 | 10.65 | 10.92 | 11.06 | 11.24 | 11.96 | 13.02 | 12.80 | 12.69 | 12.54 | 12.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.795 |
| SC2 | 0 | 8 | 8.714 |
| SC3 | -18 | 7 | 7.098 |
| SC4 | -25 | 6 | 5.755 |
| SC5 | -34 | 6 | 5.449 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.