EB-430AC4-B05 C
8.45 kW
Defrost: None
Product code: EB-145AE4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,191 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 28.8 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-145AE4-B01 C | None |
|---|---|
| EB-145AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.25 | 3.24 | 3.25 | 3.26 | 3.25 | 3.22 | 3.19 | 3.30 | 3.52 | 3.81 | 3.73 | 3.71 | 3.67 | 3.61 |
| 5 | 4.28 | 4.33 | 4.38 | 4.43 | 4.43 | 4.40 | 4.34 | 4.45 | 4.73 | 5.13 | 4.99 | 4.95 | 4.90 | 4.82 |
| 6 | 5.28 | 5.42 | 5.55 | 5.66 | 5.70 | 5.68 | 5.60 | 5.70 | 6.05 | 6.54 | 6.32 | 6.25 | 6.14 | 5.97 |
| 7 | 6.15 | 6.37 | 6.57 | 6.76 | 6.86 | 6.91 | 6.88 | 6.99 | 7.43 | 8.05 | 7.77 | 7.66 | 7.50 | 7.24 |
| 8 | 7.00 | 7.31 | 7.59 | 7.81 | 7.97 | 8.04 | 8.02 | 8.13 | 8.62 | 9.35 | 9.07 | 8.96 | 8.79 | 8.49 |
| 9 | 7.76 | 8.17 | 8.55 | 8.88 | 9.09 | 9.16 | 9.17 | 9.29 | 9.85 | 10.66 | 10.35 | 10.21 | 9.99 | 9.62 |
| 10 | 8.46 | 9.00 | 9.49 | 9.91 | 10.17 | 10.32 | 10.34 | 10.46 | 11.09 | 12.00 | 11.65 | 11.47 | 11.21 | 10.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.647 |
| SC2 | 0 | 8 | 8.129 |
| SC3 | -18 | 7 | 6.809 |
| SC4 | -25 | 6 | 5.551 |
| SC5 | -34 | 6 | 5.317 |
| A | 1017 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1017 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.